EC-based Operating Rule

Overview

EC-based Operating rules are user-defined rules that control gate operations based on EC results from GTM module. User need to use coupled Hydro/GTM binary("hydro_gtm.exe") for EC-based operating rule.

To run coupled HYDRO/GTM, provide the hydro input file and gtm input file as arguments. For instance, the command to run coupled Hydro/GTM with hydro input hydro.inp and gtm input gtm.inp is:

hydro_gtm.exe hydro.inp gtm.inp

The input file used for EC-based operating rule is the same as the ones used for general operating rules in DSM2. The use of general operating rules in DSM2 is documented in detail in Operating Rule Guide and Operating Rule.

This document specifically describes the use of EC-based Operating Rule.

Tables of Contents:

EC-based operating rule

Defines the name, action and trigger of the EC-based operating rule in OPERATING_RULE table in the input file.

OPERATING_RULE Table Field Descriptions

NAME

Same as the general operating rule. This is the identifier of the EC-based operatinf rule.

ACTION

Definition of the action to be taken when the EC-based trigger transitions from FALSE to TRUE.

TRIGGER

An EC-based trigger that activates the ACTION when it transitions from FALSE to TRUE. It can either be the name of the trigger variable or direct definition of the trigger.


EC-based oprule expression

Defines the trigger name and expression in OPRULE_EXPRESSION Table in the input file.

OPRULE_EXPRESSION Table Field Descriptions

NAME

Name for the trigger. It should be consistent with the name used in TRIGGER.

DEFINITION

Definition of the expression -- this will be a formula involving model variables. In the general operating rule, time series can be used; however, EC-based operating rule can only use model varaibles.

The trigger keyword for using EC-based operating rule is chan_ec.

Inside of the trigger keyword, users need to specify the trigger location (i.e., the channel number and the distance of the location on the channel.)


EC-based oprule example

The following example uses the EC-based operating rule to close the gate named montezuma_salinity_control when EC at location channel number 517 and distance 7876 ft exceeds 8500 ยตmho/cm.

OPERATING_RULE
NAME                 ACTION                                                                                                    TRIGGER
mscs_close           "SET gate_op(gate=montezuma_salinity_control,device=radial_gates,direction=from_node) TO 0.0"             "ec_too_high"


OPRULE_EXPRESSION
NAME                 DEFINITION
ec_too_high          "chan_ec(channel=517, dist=7876) > 8500"

The operating rule has an identifier mscs_close. The trigger name is ec_too_high, which is the same in both OPERATING_RULE table and OPRULE_EXPRESSION table. When the trigger condition becomes True, the specified Action in OPERATING_RULE table will change the gate operation.